FAQ

Our ZXOQM series fuel oil burner uses clean fuel. As long as the liquid fuel can be used, safe and trouble-free.
The installation, commissioning, operation and maintenance of the burner must be carried out by qualified technicians approved by the relevant local production safety inspection department. All work must be in accordance with relevant local standards and specifications.


Installation and maintenance must be carried out in the case of power failure and cut off the fuel supply burner into operation before you must carefully check the power supply, fuel safety status and the correctness of the connection. Any abnormalities found must be shut down for maintenance.

Our ZXOQM series fuel oil burner uses clean fuel. As long as the liquid fuel can be used, safe and trouble-free.

The installation, commissioning, operation and maintenance of the burner must be carried out by qualified technicians approved by the relevant local production safety inspection department. All work must be in accordance with relevant local standards and specifications.

Installation and maintenance must be carried out in the case of power failure and cut off the fuel supply burner into operation before you must carefully check the power supply, fuel safety status and the correctness of the connection. Any abnormalities found must be shut down for maintenance.

Our fuel oil burners can be widely used in boilers, painting ovens, hot water furnaces, incinerators, heaters, heat treatment furnaces, die-casting machines, aluminum processing equipment, food processing and other industries.

Our Burners in the pursuit of high quality at the same time, and continue to improve the service system, and strive to provide users with a full range of services and technical support.

Our ZXOQM series oil burner mainly consists of oil system, air supply system, gas system and electric power control system. The overall structure of the burner is shown in the right figure.

Fuel by the motor driven gear pump will be fuel oil transmission, through the solenoid valve control into the air cylinder through the injector nozzle and air mixing to form an atomized and fan to send the combustion air mixed with the automatic ignition combustion.

Flame detector (electronic eye) will be based on the presence or absence of combustion flame output signal to the PLC control template to determine the flame burning and extinguished. If the flame is not lit or ignited accidentally extinguished, the program will not monitor the electronic eye flow signal, that is, to determine the flame is extinguished, will immediately issue instructions to stop the fuel supply and shut down.

ZX0QM series fuel gas burners are mainly composed of three parts: air supply system, gas path system and power control system.

When the combustible gas is controlled by the control system to enter the combustion head of the burner, the primary air is mixed with the combustible gas, ignited and burned, and the secondary air assists combustion to achieve full combustion. The combustion status is detected and controlled by the flame automatic tracking system. When there is a combustion failure (lack of oxygen in the combustion chamber, combustible gas under-pressure, combustible gas flow cutoff, insufficient gas volume, etc.), the control system issues an instruction and the solenoid valve of the gas supply system is quickly closed. , cut off the gas power supply, the burner automatically purges and then shuts down, indicating a fault.

The flame detector (ion electrode) will send a signal to the controller according to whether there is an ion current signal in the combustion flame to determine whether the flame is burning or extinguishing. If the flame is not ignited or is accidentally extinguished after ignition, the controller will not be able to detect the ion current signal, that is, it will judge that the flame is extinguished, and will immediately issue a command to stop the fuel supply and shut down the machine.

ZX0QM series burners adopt mechatronics design, integrating gas supply, combustion, flame monitoring, PLC program control, etc. with the combustion fan to achieve fully automatic safety control.

The main performance features are as follows:

  1. Under the rated gas pressure, pass the rated gas volume and fully burn it to meet the rated heat load required by the boiler. The flame fills the furnace well and the combustion is complete, reducing the emission of harmful substances (CO NOX) in the flue gas.
  2. It adopts manual and automatic program control, and the operation process can realize fully automatic control. It is equipped with automatic flame monitoring and flameout protection device (ion electrode). When ignition fails or the flame suddenly goes out during operation, the burner will automatically lock and needs to be restarted. Ensure work safety.
  3. ZXOQM series burners adopt single-stage combustion control. The single-stage burner can be controlled by a temperature or pressure controller and automatically starts and stops according to the load changes of the thermal equipment.
  4. Pre-purge the furnace before ignition. The operation of ignition, ignition and adjustment is convenient, safe, reliable and low noise.
  5. Easy to install. Each burner is equipped with a slidingly adjustable mounting flange. During installation, you only need to fix the burner on the furnace mouth through the flange.
  6. ZXOQM series burners are compact in structure and easy to maintain. Maintenance and overhaul needs have been taken into consideration in the design. All parts are easy to disassemble, clean, repair and replace.

Our burner adopts electromechanical integration design, oil supply, combustian, flame monitoring, PLC program control, etc. and combustion fan into one, to realize fully automatic safety control.

The main performance characteristics are as follows:

1, Using proportional adjustment nozzle, cyclone air distribution flame stabilizing device,reasonable organization of oil mist and air flow direction, so that the atomized fuel and combustion air good mixing, to achieve stable, safe and efficient combustion.

2, The use of automatic PLC program control, the operation process can be fully automatic control. equipped with automatic flame monitoring and flame failure protection device (electronic eye), when the ignition fails or the operation of the flame suddenly extinguished, the burner will be automatically locked, you need to restart, to ensure the safety of work.

3, ZXOQM series burner adopts two-stage combustion stepless variable speed proportional adjustment control. Two-stage burner can be controlled by the temperature or pressure controller. according to the load change of thermal equipment to automatically adjust the size of the fire, and synchronized adjustment of combustion air volume to ensure full combustion, smooth and reliable operation.

4, Easy to install, each burner is equipped with a sliding adjustment of the mounting flange, installation only through the flange burner can be fixed on the furnace mouth.

5, ZXOQM series burner structure is compact, easy maintenance, the design has taken into account the need for maintenance and overhaul, all parts are easy to disassemble, cleaning, repair and replacement.

Good installation of the burner is to ensure the correct and installation of the burner with the use of the premise of regulation, generally should be installed in accordance with the following steps:.

1, The installation flange asbestos gasket mounted on the combustion cylinder, the combustion cylinder into the furnace chamber, aligned with the location of the screw holes will be mounted flange fixed to the furnace body, to confirm that the location of the furnace into the position, will be the bolts locked, to ensure that the burner is firmly

installed. Note that the burner should be installed horizontally or vertically, should not be installed at an angle.

2, After the burner body is installed, according to the design of the fuel oil inlet pipe connected to the oil pump inlet, it should be noted that the oil inlet pipe should be equipped with filters and regular cleaning of filters. Connection should be completed to check the pipeline sealing.

Special Note: Fuel storage and piping system devices and connections

construction, acceptance, etc., must strictly comply with the relevant norms and regulations of the local safety authorities, and can only be put into use after qualified acceptance.

Burner in the installation is completed, put into normal use before the professional should be debugging and safety checks, generally according to the following procedures for debugging.

  1. First check to make sure that all the preparatory work of the system is ready, after confirming the fuel gas circuit and power supply. (The first time the oil system should be put into use to exhaust air operations)

2, Tum on the power switch to start the burner (through the external control circuit start or direct start), if there is any abnormality should immediately turn off the power shutdown check.

Note: For three-phase motors, you should also confirm that the motor is running positively beforehand.

3, Confirm the operation program: observe the whole process of starting to combustion is consistent with the control program. If there is any abnormality Should immediately stop the machine to check. Confirmation of normal, you can enter the next adjustment program.

4, Combustion condition judgment: ignition success into the normal combustion state should be observed after combustion conditions, and appropriate combustion adjustment to achieve the best combustion state. Can be measured through the smoke tester or observe the smoke condition to determine the combustion state.

  1. a) lgnition is good, flame stability (no deflagration or difficult to ignite phenomenon, no deflagration, backfire phenomenon);
  2. b) Whether the exhaust smoke is normal (normal for colorless transparent exhaust smoke) combustion regulation: mainly through the wind door adjustment and oil pressure adjustment to achieve.
  3. c) One-stage burners can achieve good combustion by manually setting the parameters of the one-stage fire damper.
  4. d) Two-stage burners can achieve good combustion by manually setting

The parameters of the two-stage fire dampers.

The burner can be put into normal use after the commissioning is completed. Daily operation is carried out in the following steps.

1, Check:Confirm that the equipment system startup preparation is ready. Determined to connect the fuel, gas and power

2, Start: open the power switch to start the burner, through the external control to start the operation. The burner will automatically switch between small and large fires according to the control of the equipment control device.

3, Stop:lf you need to stop running, you can press the emergency stop button and turn off the power switch to stop. When shutting down for a long time, the oil valve should be closed and the power supply should be cut off to ensure safety.

Note:After ignition failure or accidental flameout triggers the burner fault alarm, it is necessary to restart the burner after troubleshooting.

Maintenance shall be carried out in accordance with the following requirements.

  1. Check the connection of burner and its parts frequently to see if they are tight and ifthere is any change in their position.
  2. Each time before the start to check the power supply circuit and gas circuit isabnormal and start the operation process is not abnormal.

3.often check whether the oil supply is normal, combustion is good, control system is sensitive.

  1. Pay attention to the burner working environment should be clean, dry, especially thepart of the circuit shall not be damp, subject to high temperature.
  2. Such as device filters should be cleaned regularly to ensure that the fuel access.
  3. Regularly clean ignition needle, flame monitor (electronic eye) and fuel injector.
  4. Regularly monitor the fuel nozzle, ignition needle and flame stabilizer disk positionchanges, clean up scaling or carbon deposits.

8.Regularly carry out the overall inspection, maintenance.

  1. Clean the chimney regularly to prevent blockage or smoke leakage.

Burner overhauling includes the following;

  1. Need tocheck the solenoid valve has no leakage frequently, if so should immediately check the valve sealing surface wear and whether the spool is stuck by foreign objects, if necessary, replace the new valve.
  2. Regularly dismantle and clean thefuel filter to keep it in a clean state, such as damage to the filter should be replaced immediately with a new filter, especially at the beginning of the use of the stage to pay more attention to.
  3. Check and clean the ignition electrode and electronic eye, correct its position. If there is damage should be repaired or replaced.
  4. Let the burner in the non-water-cooled furnace chamber is used during the burner shutdown. In order to prevent high temperature radiation from the furnace chamber damage to the burner, appropriate protective measures should be used.
  5. After overhauling the burner should be re-examined for safety and debugging, all normal before being put into normal use.

Our burners have the advantages of high combustion efficiency and

easy to realize automatic control, so they are widely used in industrial and civil thermal energy equipment. However, if it is used improperly, it can cause fuel leakage, deflagration and explosion, which have serious

consequences, and necessary measures should be taken to prevent accidents.

  1. The burner installation, maintenance and operation personnel must havereceived relevant technical training, mastery of relevant technologies andby the local fuel supervisor and safety production monitoring department to assess the qualifications before going on duty.
  2. The fuel system must be constructed according to the design requirements,and the materials used and the auxiliary equipments must be in accordance with the requirements of the localThe materials used, and ancillary equipment must meet the requirements of local norms and standards, after the construction is completed, according to the local safety and soil officials I female L1 day team’n to meet the design requirements before the commissioning, operation.
  3. When the burner malfunction and lock bolt, over 1 Hall T three to the year people “in the re-acquisition, to avoid forced start, many times to start the oil mist caused by the accumulation of triggering serious accidents.
  4. In order to ensure the safety of the burner and heat equipment, the burner every twenty-four hours should be at least one time within their own safety and reliability to check the opportunity to self-check are in each start-up waiting time. Therefore, the burner should be shut down at least once every 24 hours of operation, either automatically or manually.
  5. Fittings where there is a paint seal on the screws are not allowed to

disassemble, otherwise it will be damaged due to the destruction of

components leading to accidents.